Critical Safety Bulletin
Sun 6/30/2013
Tank_Explosion_852.jpg
There have been two recent incidents that illustrate possible dangers related to electrical tank heaters. One occurredatan oil and gas processing facility and another at a manufacturing facility.
The manufacturing plant incident was on a hydraulic oil storage tank that is similar to thousands in use all over the world. Because of the commonality of these systems and the prolific use of electric tank immersion heaters our firm decided to develop and publish this notice for our clients and associates.
The other recent explosion occurredatan oil and gas processing facility outside of Pittsburgh. There, a fire broke out at a complex of three natural gas storage tanks, each about 25 feet tall and 8 feet wide. The natural gas is pressurized within the tanks and moved along a pipeline to a processing plant, leaving behind a “briny fluid” made up of liquid hydrocarbon waste called condensate. The tank’s electric heaters are designed to keep the liquid mixture from freezing.
The local fire chief explained that the tank designed to hold the liquid apparently was empty or nearly empty, but still contained gas vapors. When the liquid mixture level is low, the heating element is designed to shut off. But in this case, the electric heater continued to operate, eventually warming the vapors to combustible levels, setting off the explosion.
(For more information, check out the complete article from the Pittsburgh Post-Gazette.)
IT IS AN URGENT MATTER THAT YOU IMMEDIATELY REVIEW ANY ELECTRIC TANK HEATER INSTALLATIONS FOR DESIGN AND INSTALLATION ISSUES THAT CAN LEAD TO EXPLOSIONS AND TAKE ACTION AT ONCE TO AVOID AN INCIDENT.
What to Look For
How would someone know that they might have a problem? Let’s review several key electric tank heater design and installation issues that could lead to fires or explosions if left unchecked.
Electric Bayonet Immersion Heaters
The electric heaters to be concerned about typically extend into a tank through the sidewall. They might be 12” to 36” long or longer. They are typically in the form of a bundle of elements – such as a coil, wire or other shape – which resist the electric current, causing it to give off heat. It’s the same concept used in an electric stove or toaster.
In many cases these elements work fine if they are covered with a fluid. If they are uncovered, and the watt density is high enough, then they can become an ignition source.
Watt Density and Protection
The watt density is the number of watts per square inch of heating surface or element that the designer planned for the unit selected. It makes sense that if you squeeze a whole lot of watts through a small heater, the heater elements can get very hot. The free air temperature of some of these elements can be over 1,000°F. Remember, the flash point of many hydraulic oils and other hydrocarbons is only 400 to 600°F.
It is not just oil tanks that are an area of concern. Any tank that can accumulate flammable elements must be considered. For instance, a wastewater tank that drains machining fluids may primarily contain water. But just a small amount of oil mixed in can still cause a problem. The oil can be thermally cracked or broken down under certain conditions filling the vapor space of the tank with hydrocarbon fumes. Then when the level changes in the tank and air is brought in, a flammable mixture can be created.
Consider also the case of a wastewater tank that is part of a sewage system or even a food process. Whenever biological activity consumes organic materials, methane can be released. If the elements become exposed and there are no protections in place, you can create an ignition source directly in the tank.
The Fire Triangle
The fire triangle concept is that when you bring fuel, oxygen and an ignition source together you have all of the elements needed for a fire. When a flammable mixture is confined and ignited, you have everything you need for an explosion. The flammable materials try to expand to many times their volume in fractions of a second. When they cannot escape whatever vent is provided in a timely manner the vessel or tank is pressurized and usually comes apart at some weak point. Often for cylindrical tanks, this weakest point is at the top of the container. If an explosion does occur, the flying metal and resulting fireball can be deadly and destructive.
Strategies for Safety
You must verify that you have minimized risks related to electric tank heaters wherever they are installed. Methods to minimize risks include the following:
1. Verify watt densities and maximum temperatures
There are many options available when buying electric heaters. You can purchase heaters that have features to minimize the maximum temperature, or you can specify lower watt densities.
2. High temperature limit controllers
There are operating temperature controllers and high temperature limit controllers. Operating controllers are essentially like thermostats at your home. They seek to provide the right temperature on a routine basis. High temperature limit controllers are a special separately installed control that has a manual reset feature once exceeded. In this case, the device shuts the unit off until a person manually hits a button or takes some action before the unit will run again. This feature forces someone to investigate and hopefully understand that some unusual event occurred and that an unsafe condition was reached. If a high temperature limit is installed the setting has to be well below whatever flash point could be reached.
3. Level controller/low level shut offs
There are level controls available that help ensure minimum levels are maintained in tanks for the heaters to operate. Level controls, however, are sometimes difficult to maintain. There are many things that can fool them. In the case of boilers there are usually two level controllers: one as a primary and one as a back-up for this reason. It would never be a good idea to rely only on level controls for the safety of your system, but it would be an extra layer of protection over and above a high temperature limit device.
4. Tank design and maintenance
Tank system design needs to also be considered. There are several national safety code standards for fuel oil tanks that call out venting requirements. In some cases, relief valves might also be required. In most cases the vents for oil systems are larger than one might otherwise consider. Remember that when replacing elements, care must be taken to consider watt densities and safety controls. There also needs to be consideration for how safety devices might be wired. In all cases safety devices should be again checked whenever elements are replaced. The National Fire Protection Association’s (NFPA) codes could be a good starting point for investigating tank issues. NFPA 22 in particular has information about tank heating systems that might be helpful.
5. Preventive maintenance/safety device testing
There was a tank explosion at an offshore facility in 2009 which was identified to have occurred because of the corrosion of a protective sheath on an electric heater. This incident illustrates the need to conduct periodic inspections of “at risk” electric heating elements and for testing of level controls and high temperature limits.
There are no published guidelines that we are aware of regarding the testing and inspection of these devices. However, most combustion equipment codes and standards call for at least annual testing of safety interlock devices. The implementation of a testing and inspection program for electrical heaters in tanks needs to be risk based for the application and should consider what is installed, the watt density, the materials in the tank, and other factors such as operating levels versus tank volume.